说明
告警开关数据推送
接口地址
POST {用户API接口地址}?type=3ph&cmd=breaker0&appid={AppID}
请求参数说明
| 名称 | 类型 | 必填 | 说明 |
|---|---|---|---|
| appid | string | Y | 管理员给用户创建的应用ID |
Body 示例
{
"gwsn": "94A9901BB884",
"cmd":"breaker0",
"key":"get",
"bresn":"00600041350F4E3134525348",
"settings1": {
"timer1": true,
"timer2": true,
"timer3": false,
"timer4": false,
"timer5": false,
"timer6": false,
"timer7": false,
"timer8": false,
"lock_model": false,
"remote_lock": false,
"power_up_off": true,
"power_up_on": false,
"mcu_over_temperature_alarm": false,
"over_voltage_alarm": false,
"over_voltage_open": false,
"under_voltage_open": false
},
"settings2": {
"over_current_off": false,
"remaining_power_off": false,
"line_over_temperature_alarm": false,
"line_over_temperature_off": true,
"leakage_current_alarm": false,
"leakage_current_off": true,
"under_voltage_alarm": false,
"fire_event_off_alarm": true,
"over_load_access_alarm": false,
"over_load_access_off": true
}
}字段说明:
| 字段名称 | 类型 | 说明 |
|---|---|---|
| gwsn | string | 网关序列号 |
| bresn | string | 断路器序列号 |
| key | string | get:获取,set:设置 |
| cmd | string | 固定 breaker0 |
| settings1 | object | Y |
| settings2 | object | Y |
settings1 字段说明
| 字段名称 | 类型 | 说明 |
|---|---|---|
| timer1 | bool | 启用/关闭 ,定时任务1 |
| timer2 | bool | 启用/关闭,定时任务2 |
| timer3 | bool | 启用/关闭,定时任务3 |
| timer4 | bool | 启用/关闭,定时任务4 |
| timer5 | bool | 启用/关闭,定时任务5 |
| timer6 | bool | 启用/关闭,定时任务6 |
| timer7 | bool | 启用/关闭,定时任务7 |
| timer8 | bool | 启用/关闭,定时任务8 |
| lock_model | bool | 启用/关闭,分闸解锁模式切换功能;=0分闸闭锁=1分闸解锁(Lockmodel) |
| remote_lock | bool | 启用/关闭,远程挂锁功能 |
| power_up_off | bool | 启用/关闭,上电分闸功能 |
| power_up_on | bool | 启用/关闭,上电合闸功能 |
| mcu_over_temperature_alarm | bool | 启用/关闭,MCU芯片过温告警 |
| over_voltage_alarm | bool | 启用/关闭,过电压告警 |
| over_voltage_open | bool | 启用/关闭,过电压分闸 |
| under_voltage_open | bool | 启用/关闭,欠电压分闸 |
settings2 字段说明
| 字段名称 | 类型 | 说明 |
|---|---|---|
| over_current_off | bool | 启用/关闭,过电流分闸 |
| remaining_power_off | bool | 启用/关闭,剩余电量分闸动作(开发中) |
| line_over_temperature_alarm | bool | 启用/关闭,出线端子过温告警 |
| line_over_temperature_off | bool | 启用/关闭,出线端子过温分闸 |
| leakage_current_alarm | bool | 启用/关闭,漏电流告警 |
| leakage_current_off | bool | 启用/关闭,漏电流分闸 |
| under_voltage_alarm | bool | 启用/关闭,欠电压告警 |
| fire_event_off_alarm | bool | 启用/关闭,故障电源触发分闸动作告警 |
| over_load_access_alarm | bool | 启用/关闭,过负荷接入告警 |
| over_load_access_off | bool | 启用/关闭,过负荷触发分闸 |
返回数据
返回 200 状态码即可